What are the common problems encountered by fan coil units during testing?

Views : 1957
Update time : 2020-02-20 16:46:02
Fan coil unit of central air conditioner
What are the common problems encountered by fan coil units during testing?

1. As there is no requirement for the proportion of the third-gear air volume of fan coil units in the previous standards, the static pressure in the national standard requires the units to specify the static pressure value for the third-gear air volume.  In the selection of motors, the proportion of third-gear air volume has not been adjusted properly. Some fan coil units and even the third-gear air volume have almost no difference. Some high and middle-gear air volumes have not been opened or the low-gear air volume is too small. These do not meet the requirements of users.

2. In order to meet the air volume requirement when the outlet static pressure is 12Pa, the power of the motor is simply increased, resulting in the air volume reaching the target but the cooling capacity not reaching the rated value.

3. Some fan coil units did not improve the surface cooler in order to reach the standard of cooling capacity, and the air volume exceeded the standard requirements too much, resulting in the noise value far greater than the standard specified value, which is quite common.

4. If inferior motor is selected, when detecting the noise of the unit with static pressure requirements, the motor will roar.

5. The size of the wind wheel selected by the fan coil unit is too large or too small to meet the static pressure requirements, especially the selection of the impeller of the small air volume unit should be more cautious.

fan coil unit price, chilled water fan coil units, fan coil unit, ceiling fan coil, cassette fan coil unit, floor standing fan coil unit, ultra thin fan coil unit,fan coil unit factory, fan coil price
Related News
Read More >>
Water source rooftop chiller unit part in HAVC Water source rooftop chiller unit part in HAVC
Mar .22.2024
The fan coil unit is a common HVAC system terminal device. It can be used independently or in conjunction with other equipment to provide more efficient cooling and heating services. One such example is the water-source chiller.
The quietness and efficiency of Guqin series Horizontal Ultra-Thin Concealed fan coil units The quietness and efficiency of Guqin series Horizontal Ultra-Thin Concealed fan coil units
Mar .22.2024
The Guqin Series Vertical and Horizontal Ultra-Thin Concealed Fan Coil Unit is a HVAC terminal component product produced by Yesncer, named after the world’s intangible cultural heritage – the Guqin. Not only does it have an exquisite appearance, but its
Ultra-low temperature air source heat pump principle and core technology Ultra-low temperature air source heat pump principle and core technology
Dec .27.2023
The principle of ultra-low temperature heat pump system is as follows.
Fan Coil Unit Selection And Product Advantages Fan Coil Unit Selection And Product Advantages
Dec .07.2023
Fan Coil Unit Selection And Product Advantages
This website uses cookies
We use essential cookies to make our site work. With your consent,we may also use non-essential cookies to improve user experience and analyze website traffic. By clicking "Yes",you agree to our website's cookies use as described in our "Privacy Statement".