Common Faults And Elimination Methods of Fan Coil Unit 2
Views : 1944
Update time : 2020-03-18 15:58:04
Common Faults of Fan Coil Unit and Their Elimination Methods
Fault 6, Fan Coil Unit Leakage
Cause:
Fan coil unit wires are damaged and leaking electricity.
Exclusion method:
Repair of Fan Coil unit Line
Fault 7, Fan Coil unit Leakage
Cause:
1, installation is not good
2, water tray tilt
3, drain plug
4, pipe has a leak
5, condensate dripping from the pipe
6, fan plate pipe joint installation is not good
7, exhaust valve forgot to close
Exclusion method:
1, fan coil unit horizontal installation
2. Adjustment
3, remove the blockage
4, check and replace the fan coil pipe
5, check the heat preservation again
6. Fasten after inspection
7. Close the valve
Fault 8: The fan will not stop after the fan coil unit is turned off.
Cause:
1, switch failure
2, control circuit short circuit
Exclusion method:
1, repair or replace the fan coil unit switch
2, check the fan coil unit circuit, eliminate short circuit
Fault 9. Fan coil unit has vibration and noise
Cause:
1, installation is not good
2, casing installation is not good
3. Loose parts for fixing fan coil units
4. There are foreign matters in the passage of fan coil unit air
5, fan motor failure
6, fan blade damaged
7. Loose louver of fan coil unit air supply outlet
8. Air in Fan Coil Unit
9, fan coil unit chilled water (hot water) flow too fast
10, there is a lot of air into the water
11, when using quantitative valve, differential pressure is too large
Exclusion method:
1. Reinstall and adjust
2. Reinstall
3. Fastening
4. Removal of Foreign Bodies
5, repair or replace the motor
6. Replacement
7. Fastening
8. Exhaust air
9, check the water flow rate
10. Remove air from water
11, replace the appropriate valve
Fault 10, fan coil unit cold air (hot air) effect is not good
Cause:
1, valve opening is not enough
2, pipe coil pipe blockage, poor ventilation
3. Air in Fan Coil Unit
4. Power supply voltage drops
5, air filter blockage
6. Insufficient water supply (cold and hot water)
7. Abnormal water supply temperature
8, fan reverse
9, air supply, air return has a barrier
10. The front plate is not installed properly.
11, air short circuit
12, indoor air distribution is uneven
13. Improper selection of fan coil unit model
14, ceiling ceiling fan coil units connected to the air leakage
15, improper fan coil unit temperature adjustment
16, room sunshine or open the window
Exclusion method:
1, readjust the opening
2, cleaning the coil
3. Exhaust air
4, find out the reason
5. Clean the air filter
6, adjust the water supply valve
7, check the frozen water (or hot water) temperature
8. Re-wiring
9. Remove obstacles
10. Regular installation
11, check the tuyere for obstacles
12, check and adjust the tuyere
13. Redesign and select the wind turbine
14. Repair
15, readjust the air supply level
16. Close the window and hang the curtain
Summary: The installation of fan coil units is a task with high responsibility and technical requirements for construction personnel. Production, sales and after-sales service will also encounter various related problems, so Baoding Yuexin has certain requirements for personnel training and management within the company. If you have any questions, you can contact us Baoding Yuexin Fan Coil Unit.