What are the reasons of noise, temperature deviation and water leakage of fan coil units?

Views : 1155
Author : sherry
Update time : 2020-11-07 13:41:45
First of all,A fan coil unit, the air volume is small, poor cooling capacity:
When the fan is in normal operation, the air duct air leakage is rare and easy to handle, and the small air inlet is mostly caused by the blockage of the filter screen at the return air outlet. The solution is to clean the filter screen frequently. If it is not cleaned in time, dust and sundries will further stick to the coil fins and wind wheel blades. If the fins are blocked by dirt, the ventilation capacity of the fan will decrease. Dust will also accumulate on the fan impeller, resulting in smaller blade angle, lower air volume and higher fan current. Therefore, it is very necessary to clean the filter screen of the air return port. Generally, it should be cleaned at least once every quarter, otherwise the blockage will become more and more serious and the maintenance will become more and more difficult.

Secondly, the fan coil noise:
There are some reasons for the high noise of fan coil. When the coil is in operation, its blades, fan, fan shaft and unit shell are in vibration state. If the coil is used for a long time, the surface of its components will have turbidity embroidery and oil stains, which will make the components friction and vibrate violently, and the released noise will be relatively large. When there is air flowing inside the coil unit, noise will be generated when it passes through the return air filter screen, the air moves in the unit, the wind blows the fins of the heat exchanger and the air moves in the fan.

Common reasons of loud noise of fan coil unit:
1, the fan coil unit installation is not firm, causing system resonance;
The fan motor bearing is worn, which causes the fan motor to run eccentrically and produce noise;
The fan blades deform and scrape other parts;
During transportation or installation, the fan coil unit is deformed, which makes the fan bearing or bearing seat out of center and produces noise.
It has a great relationship with the winding of the motor itself. If there is no fundamental change in the high-speed gear after replacing the capacitor, it is recommended to replace the motor directly.
Three, fan coil motor does not turn: Check whether the fan coil unit power supply is normal by powering on; if there is no power output, check whether the power supply is faulty; Then check the speed control switch. If the above two conditions are not true, check whether the impeller is stuck. Because the electric power of the fan coil unit is relatively small, a little resistance may be stuck. At this time, we need to observe and check in time. Contact the maintenance personnel immediately.
Four, fan coil air volume is normal, supply air temperature deviation: Most of these faults occur in the coil water supply and return system. First, check whether the water supply temperature and water quantity are normal. If the temperature difference between supply and return pipe is large, it is mostly caused by blockage of inlet filter or gas in pipeline. In addition, sharp bends, slag deposit points and gas gathering points should be avoided as far as possible in the construction process. Although the specification requires that exhaust valves and sewage valves should be set at high points and low points, it is often difficult to realize them in the construction site. Flush and drain as much as possible after installation. Clean the water filter frequently during operation to keep the pipeline unblocked. Five, fan coil water leakage:
1. If the water leaks out of the fan coil water collecting tray, it is mainly because there is something wrong with the insulation material, which needs to be strengthened and can be eliminated.
2. If the water leaks in the water collecting tray, it means that the condensate pipe of the fan coil unit is not smooth, and the condensate overflows. We only need to dredge the condensate pipe, or purge it with a gas cylinder.
3. If the condensate drain pipe is always blocked, water will often leak from it. In addition to cleaning it regularly, it is recommended to wash and scale it thoroughly, and check whether the filter screen is added to the air return outlet of the fan coil unit and whether the installation slope of the pipe meets the requirements.


 
Related News
Read More >>
Water source rooftop chiller unit part in HAVC Water source rooftop chiller unit part in HAVC
Mar .22.2024
The fan coil unit is a common HVAC system terminal device. It can be used independently or in conjunction with other equipment to provide more efficient cooling and heating services. One such example is the water-source chiller.
The quietness and efficiency of Guqin series Horizontal Ultra-Thin Concealed fan coil units The quietness and efficiency of Guqin series Horizontal Ultra-Thin Concealed fan coil units
Mar .22.2024
The Guqin Series Vertical and Horizontal Ultra-Thin Concealed Fan Coil Unit is a HVAC terminal component product produced by Yesncer, named after the world’s intangible cultural heritage – the Guqin. Not only does it have an exquisite appearance, but its
Ultra-low temperature air source heat pump principle and core technology Ultra-low temperature air source heat pump principle and core technology
Dec .27.2023
The principle of ultra-low temperature heat pump system is as follows.
Fan Coil Unit Selection And Product Advantages Fan Coil Unit Selection And Product Advantages
Dec .07.2023
Fan Coil Unit Selection And Product Advantages