Calculation of static pressure box
static pressure box control wind speed should not be greater than 1.5 m/S.
the cross-sectional area of air outlet is A=G/V(G is the air supply volume), and the cross-sectional areas in all directions should be the same
In general system, the static pressure box can be replaced by tuyere reducing and silencer
 
Determination of ventilation frequency of smoke control and exhaust
fire pump room is not less than 4 times
5-8 times in substation room
substation room 5-8 times
 
Layout of smoke exhaust port
corridor more than 60 meters, do smoke outlet
The front room of the elevator uses normally open multi-leaf air supply outlets, one for each floor
Self-hanging louver tuyeres are used in stairwells, and one is set on floors 2-3
 
Air pressure state of the room
the air-conditioned room in the building should maintain positive pressure.
Negative pressure should be maintained in toilets, washrooms and all kinds of equipment rooms in buildings
Positive pressure should be maintained in hotel rooms and negative pressure should be maintained in washrooms
Positive pressure should be maintained in the front hall of the restaurant, negative pressure should be maintained in the kitchen, and air pressure in the restaurant should be between the front hall and the kitchen.
 
Layout principle of air duct in suspended ceiling
From top to bottom: smoke exhaust duct, exhaust duct, air delivery duct and water pipe
 
Relative position of air supply and exhaust ports
When air supply and exhaust ducts are parallel in fan coil unit air-conditioned rooms, the air supply and exhaust outlets should not be arranged side by side as far as possible, but should be staggered
 
Design of air supply pipe
Try to keep the wind from going backwards in the air supply pipe to ensure good air flow and air outlet effect in the pipe
 
Overlapping of tee and air duct
The pipe diameter connected with the tee should be consistent with the diameter of the tee, so as to avoid excessive local loss.
Related News
Read More >>
Water source rooftop chiller unit part in HAVC Water source rooftop chiller unit part in HAVC
Mar .22.2024
The fan coil unit is a common HVAC system terminal device. It can be used independently or in conjunction with other equipment to provide more efficient cooling and heating services. One such example is the water-source chiller.
The quietness and efficiency of Guqin series Horizontal Ultra-Thin Concealed fan coil units The quietness and efficiency of Guqin series Horizontal Ultra-Thin Concealed fan coil units
Mar .22.2024
The Guqin Series Vertical and Horizontal Ultra-Thin Concealed Fan Coil Unit is a HVAC terminal component product produced by Yesncer, named after the world’s intangible cultural heritage – the Guqin. Not only does it have an exquisite appearance, but its
Ultra-low temperature air source heat pump principle and core technology Ultra-low temperature air source heat pump principle and core technology
Dec .27.2023
The principle of ultra-low temperature heat pump system is as follows.
Fan Coil Unit Selection And Product Advantages Fan Coil Unit Selection And Product Advantages
Dec .07.2023
Fan Coil Unit Selection And Product Advantages