News Center

What are the types and common faults of fan coil units?

Views : 995
Author : Sherry
Update time : 2021-10-28 10:13:32
I.Classification of fan coil units
1. Horizontal concealed fan coil unit:
It is suitable for places with relatively high decoration grade and for initial installation, but it is not suitable after the decoration is completed, because it is a concealed project, which is usually used in central air-conditioning projects.

2. Cassette fan coil unit:
Cassette fan coil has ABS panel, while ordinary fan coil is only galvanized on its surface, which is mainly beautiful in appearance and contains sound-absorbing sponge. It has low noise and does not need other accessories, such as air outlet and metal hose. Because its air distribution is limited, the installed floor height is generally no more than 3.5 meters, otherwise it will cause short circuit of space. In addition, it has its own panel and condensate lift pump.

3. Vertical exposed fan coil unit:
Its advantages are that it can directly replace radiator, and it is quick in effect and small in size. It is suitable for places that have been decorated or not decorated, and its flexibility is better than that of vertical open-air fan.

4. ceiling and suspending fan coil unit:
Including suspended ceiling type and vertical type, they can be hung on the top or stand on the ground, which is beautiful in appearance and suitable for places with high decoration grade, such as some completed commercial places, restaurants and so on.

5. Cabinet flooring standing fan coil unit:
It is also commonly known as water air conditioning in northern China. The range and air volume are higher than those of the vertical open-air fan. The air supply distance is generally more than 5 meters, and the air volume can be sent to 1,000 to 2,000 cubic meters. It is suitable for large space places with low decoration requirements, such as restaurants, conference rooms, living rooms and so on.


6. High static pressure fan coil unit with Jet:
Generally, coils with high static pressure are used, so the outlet air speed is relatively large, and the air supply distance is relatively long. If it is normal, there is no problem when it is 10 to 15 meters. Workshops, canteens, exhibition halls, etc. that span within 40 meters can directly use two jet fans.

7. Four-pipe fan coi:
Four-pipe fan coil has two sets of water pipes connected with cold water and hot water respectively, that is, refrigeration and heating can be switched at any time all year round, which can realize heating in part of space and cooling in part of room, so its standard is high and its cost is naturally high.
II.The common fault of the fan coil unit
Failure treatment of air conditioner without refrigeration.
1. Open the exhaust valve of coil fan and check whether the circulating water temperature of the system is normal.
2. Check whether the two-way valve is normally opened, if not.                                          3. Check whether the filter screen of pipeline Y filter is blocked.
4, check whether the import and export temperature difference is normal, check whether the doors and windows are closed; Check whether there is dust on the air inlet filter screen and whether the fan speed is normal.
Treatment of water leakage in air conditioner.
1. Check the water leakage point to see if it is leaking or condensed water produced by itself.
2. Poor drainage: Check whether the mop pan is blocked and whether the slope is reasonable.
3. Check whether the insulation layer is broken.
4. Check whether the exhaust valve is closed and leaking.
5. Check whether the hose, valve, two-way valve, Y filter and pipeline are leaking.
Trouble shooting of air-conditioning tuyere without wind.
1. Check whether the three-speed switch is damaged; Measure whether there is electricity at the input end and output end of the temperature control switch with an electric pen, and replace or repair it if it is judged that the temperature control switch is damaged.                2. check whether the motor running speed is normal.
Performance and treatment of air conditioning noise failure.
1. Noise caused by bearing damage: replace the bearing.
2. Noise caused by ceiling during operation: adjust the height of hanger rod nut of coil fan, or deal with the friction between tuyere and ceiling keel.
3. Noise caused by air in the pipeline: the air in the pipeline is exhausted at the exhaust valve of coil fan, floor exhaust valve and terminal exhaust valve.
Treatment method of air conditioner with peculiar smell.
1. Check and clean the air inlet filter.                                                                                                                                                                                                2. Check whether there is dust on the coil fins, and clean them if there is dust.                                                                                                                         
3. Check whether there are foreign bodies, dust and accumulated water in the air duct, and clean them to remove peculiar smell.
 
Related News
Read More >>
Water source rooftop chiller unit part in HAVC Water source rooftop chiller unit part in HAVC
Mar .22.2024
The fan coil unit is a common HVAC system terminal device. It can be used independently or in conjunction with other equipment to provide more efficient cooling and heating services. One such example is the water-source chiller.
The quietness and efficiency of Guqin series Horizontal Ultra-Thin Concealed fan coil units The quietness and efficiency of Guqin series Horizontal Ultra-Thin Concealed fan coil units
Mar .22.2024
The Guqin Series Vertical and Horizontal Ultra-Thin Concealed Fan Coil Unit is a HVAC terminal component product produced by Yesncer, named after the world’s intangible cultural heritage – the Guqin. Not only does it have an exquisite appearance, but its
Ultra-low temperature air source heat pump principle and core technology Ultra-low temperature air source heat pump principle and core technology
Dec .27.2023
The principle of ultra-low temperature heat pump system is as follows.
Fan Coil Unit Selection And Product Advantages Fan Coil Unit Selection And Product Advantages
Dec .07.2023
Fan Coil Unit Selection And Product Advantages